2007Preventable

    Deutsche Bank Building Fire

    New York City, NY, USA

    Date
    2007
    Failure Category
    Standpipe Failure
    Documented Failure
    Standpipe Cut/Disconnected

    What Happened

    On August 18, 2007, a seven-alarm fire erupted in the condemned Deutsche Bank Building at 130 Liberty Street in Lower Manhattan, which was being dismantled after 9/11 damage. Firefighters connected to the standpipe and got nothing: a section of the standpipe had been cut and disconnected in the basement during demolition, and the breach had gone undetected because required inspections were not performed. Crews had to hand-stretch hose up many floors without water. The fire killed two FDNY firefighters and led to criminal charges and sweeping inspection reforms.

    Preventable with NFPA 14 / 25 Testing

    Our analysis classifies this failure as preventable: the deficiency that delayed or defeated fire suppression is the kind that routine inspection, testing, and maintenance under NFPA 25 (and, for standpipe systems, acceptance and periodic testing under NFPA 14) is specifically designed to detect. Equipment failures like this do not announce themselves — they are found by flowing water on a schedule, or they are found during a fire.

    About Standpipe Failure Failures(9 in this database)

    In any building taller than hose can be stretched from the street, firefighters depend entirely on the standpipe to move water to the fire floor. Cut or disconnected piping, clogged lines, misadjusted pressure-reducing valves, closed valves, and drained systems have all killed firefighters. NFPA 14 governs standpipe design and acceptance testing; NFPA 25 requires periodic inspection and five-year full-flow testing to prove the system still delivers its designed pressure and volume.

    Related Incidents

    View all 37 documented incidentsData sourced from NIOSH, NFPA, FEMA, FM Global, and public court records.

    Would Your System Pass Today?

    This failure was preventable. Routine NFPA 14 & 25 standpipe flow tests and hydrant inspections find failures like this one before a fire does — and keep your insurance coverage intact.