2011Preventable

    Medical Building Fire (NIOSH F2011-18)

    Asheville, NC, USA

    Date
    2011
    Failure Category
    Standpipe Failure
    Documented Failure
    No Water / Lack of Pressure in Stairwell Standpipe

    What Happened

    On July 28, 2011, fire broke out in a five-story medical building in Asheville, North Carolina. Interior crews connected to the stairwell standpipe and got no water — a failure documented in NIOSH firefighter fatality investigation F2011-18. A fire captain died after running out of air while operating without a working hoseline. The NIOSH report cites the standpipe water supply failure among the contributing factors and recommends verifying standpipe operability — precisely what NFPA 14 acceptance tests and NFPA 25 five-year flow tests are designed to do.

    Preventable with NFPA 14 / 25 Testing

    Our analysis classifies this failure as preventable: the deficiency that delayed or defeated fire suppression is the kind that routine inspection, testing, and maintenance under NFPA 25 (and, for standpipe systems, acceptance and periodic testing under NFPA 14) is specifically designed to detect. Equipment failures like this do not announce themselves — they are found by flowing water on a schedule, or they are found during a fire.

    About Standpipe Failure Failures(9 in this database)

    In any building taller than hose can be stretched from the street, firefighters depend entirely on the standpipe to move water to the fire floor. Cut or disconnected piping, clogged lines, misadjusted pressure-reducing valves, closed valves, and drained systems have all killed firefighters. NFPA 14 governs standpipe design and acceptance testing; NFPA 25 requires periodic inspection and five-year full-flow testing to prove the system still delivers its designed pressure and volume.

    Related Incidents

    View all 37 documented incidentsData sourced from NIOSH, NFPA, FEMA, FM Global, and public court records.